BROAG 610-7 BOILER SET BROAG 610-7 AIR/DIRT SEP. AND STRAINERS? BOILER SET REVISIONS SV CLIENT BELLWAY HOMES - THAMES GATEWAY Osprey House, Crayfields Bus. Pk. New Mill Road, Orpington Kent BR5 3QJ AAV CONSULTING ENGINEER SIZES? CONTRACT OCEAN ESTATE - BLOCK 'F' Dongola Road, Stepney London, E1 4QR DRAWING TITLE CHP AND BOILER PLANTROOM SCHEMATIC SV COPYRIGHT C This drawing is copyright and may not be altered, reproduced, copied, lent borrowed or sold without the express permission of C.Watkins Plumbing Ltd. RELATED DOCUMENTS This drawing should be read with the appropriate Specification (s) and Schedule (s) and all other standard documentation. WARNING Do Not Scale from this drawing. Verify all dimensions, levels and structural details on site. ASSUME THIS SET-UP IS OK? 3 No. CONNECTIONS TO STORE? FOURTH CONNECTION BYPASSES BETWEEN FLOW AND RETURN WITH NO REGULATION/ISOLATION? 3 PORT VALVE PURPOSE AND POSITION? FLOW CONN FROM CHP IN BOTTOM OF STORE THEN OUT TOP TO HEADER - OK? FOR APPROVAL DRAWN DATE 23.06.2012 SCALE APP. NTS DRG No. M. Keenan D. Pay M678 - 044 Rev