Wall-hanging refrigeration units EVO-COOL® GB Technical description Technical document 6008315-01 GB General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 1 GB Right reserved to make technical changes! Version 04.15 GB Table of contents 1. General notes 2. Technical data EVO-COOL® refrigeration units 3. Technical data EVO-COOL® deep-freeze units 4. Capacity EVO-COOL® refrigeration units 5. Capacity EVO-COOL® deep-freeze units 6. Dimensions installation size 1 CS 500, CS 900, CS 1300, CS 1500, FS 900, FS 1200, FS 1400 7. Dimensions installation size 2 CS 2000, CS 2500, CS 3000, FS 2000, FS 2500, FS 3000 8. Tendering text EVO-COOL® refrigeration units 9. Tendering text EVO-COOL® deep-freeze units General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 16 GB Right reserved to make technical changes! GB 1. General notes The Viessmann wall-hanging units EVO-COOL® are suitable for cooling and deep-freezing (634 - 3020 W) and available in 13 performance categories. EVO-COOL® is characterized by a low noise, low weight and ease of cleaning by micro-channel heat exchanger. Defrost is carried by hot gas bypass for more energy efficiency. Manufactured according to EN standards, CE-conformity. - Defroster drain tubing with electrical heating unit Defrost water evaporation plate with safety run-off Electronic temperature control Hot gas defrost Condenser with variable speed fan and a microchannel heat exchanger Control with text display, self diagnosis, remote maintenance Bus operation, USB data transfer and internet connectivity Potential-free alarm, audible alarm when faults, with fault memory Connection for door contact switch Cable with earthing contact plug or CEE socket Hermetically sealed condenser with winding protection switch and unloaded start Thermostatic expansion valve Collector dryer Pressure safety monitor, timed defrost by hot gas with safety temperature monitor or air defrosting at coldroom temperature higher than +5 ° C (adjustable) Pump-out function (activated) 5 m cable with earthing contact (CS 0500, 0900, 1300, 1500, 2000) 700 mm cable with CEE socket (CS 2500, 3000) Surfaces STA = Viessmann Standard white powder coating, galvanized steel coating with antimicrobial Viessmann SmartProtec® powder coating (similar to RAL 9016). EST = Austenitic stainless steel (material no. 1.4301) special version, polished or brushed. - on request Optional - Data logger filter fabric Winter regulation Sound-insulated housing design Sound-insulated design scroll compressor (only by FS 2000, 2500, 3000) General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 17 GB Right reserved to make technical changes! GB 2. Technical data EVO-COOL® refrigeration units Designation CS 500 CS 900 CS 1300 CS 1500 Coldroom temperature adjustment range -5°C to +20°C -5°C to +20°C -5°C to +20°C -5°C to +20°C Ambient temperature permissible +1°C to +43°C +1°C to +43°C +1°C to +43°C +1°C to +43°C 1 1 1 1 Cooling capacity (DIN EN 14511) 634 W 1050 W 1350 W 1505 W Refrigerant R134a R134a R134a R134a Refrigerant amount 500 g 650 g 1030 g 1190 g electronic electronic electronic electronic Voltage / Phases / Frequency 230 V / 1 / 50 Hz 230 V / 1 / 50 Hz 230 V / 1 / 50 Hz 230 V / 1 / 50 Hz Nominal consumption / Fuse 334 W / 16 A 567 W / 16 A 660 W / 16 A 720 W / 16 A 790 x 440 x 1013 mm 790 x 440 x 1013 mm 790 x 440 x 1013 mm 790 x 440 x 1013 mm 45 kg 54 kg 58 kg 61 kg 375 m³/h 787 m³/h 1332 m³/h 1453 m³/h 24,7 dB (A) 25,4 dB (A) 28,4 dB (A) 27,3 dB (A) Size Control Dimensions (H x W x D) Weight Min. exhaust air volume [m3/h] at ambient temperature 32 °C and heat increase of 5 K Sound pressure level¹) Connection / length of power cable With earthing contact With earthing contact With earthing contact With earthing contact /5m /5m /5m /5m Protection class IP 24 IP 24 IP 24 IP 24 Compressor type Reciprocating piston Reciprocating piston Reciprocating piston Reciprocating piston Hot gas Hot gas Hot gas Hot gas Pressostat switch point Off 18 bar Off 18 bar Off 18 bar Off 18 bar Pressostat switch point thermostatic expansion valve thermostatic expansion valve thermostatic expansion valve thermostatic expansion valve Refrigeration unit with control Item no. 00173900 00173901 00173902 00173903 Refrigeration unit with remote control 7,5 m - Item no. 00199560 00199561 00199562 00199563 Refrigeration unit with remote control 15 m - Item no. 00199580 00199581 00199582 00199583 Refrigeration unit with bus operation - Item no. 00173380 00173381 00173382 00173383 Defrosting 1) Level of sound pressure measurements taken at a distance of 10 m during ambient temperature 25°C. Depending on local conditions and installation, values can be reached above the levels given. General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 18 GB Right reserved to make technical changes! GB Designation CS 2000 CS 2500 CS 3000 Coldroom temperature adjustment range ( °C) -5°C to +20°C -5°C to +20°C -5°C to +20°C Ambient temperature permissible +1°C to +43°C +1°C to +43°C +1°C to +43°C 2 2 2 Cooling capacity (DIN EN 14511) 2035 W 2440 W 3010 W Refrigerant R134a R134a R134a Refrigerant amount 1300 g 1650 g 1700 g electronic electronic electronic Voltage / Phases / Frequency 230 V / 1 / 50 Hz 400 V / 3 / 50 Hz 400 V / 3 / 50 Hz Nominal consumption / Fuse 1050 W / 16 A 1170 W / 16 A 1300 W / 16 A 996 x 640 x 1239 mm 996 x 640 x 1239 mm 996 x 640 x 1239 mm 105 kg 107 kg 109 kg Min. exhaust air volume [m3/h] at ambient temperature 32 °C and heat increase of 5 K 1635 m³/h 2059 m³/h 2967 m³/h Sound pressure level¹) 33,4 dB (A) 39,9 dB (A) 37,4 dB (A) With earthing contact /5m CEE / 0,7 m CEE / 0,7 m Protection class IP 24 IP 24 IP 24 Compressor type Reciprocating piston Reciprocating piston Reciprocating piston Hot gas Hot gas Hot gas Pressostat switch point Off 18 bar Off 18 bar Off 18 bar Pressostat switch point thermostatic expansion valve thermostatic expansion valve thermostatic expansion valve Refrigeration unit with control Item no. 00173904 00173905 00173906 Refrigeration unit with remote control 7,5 m - Item no. 00199564 00199565 00199566 Refrigeration unit with remote control 15 m - Item no. 00199584 00199585 00199586 Refrigeration unit with bus operation - Item no. 00173384 00173385 00173386 Size Control Dimensions (H x W x D) Weight Connection / length of power cable Defrosting General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 19 GB Right reserved to make technical changes! GB 3. Technical data EVO-COOL® deep-freeze units Designation FS 900 FS 1200 FS 1400 -5°C to -25°C -5°C to -25°C -5°C to -25°C +1°C to +43°C +1°C to +43°C +1°C to +43°C 1 1 1 Cooling capacity (DIN EN 14511) 940 W 1250 W 1410 W Refrigerant R404A R404A R404A Refrigerant amount 690 g 760 g 950 g electronic electronic electronic Voltage / Phases / Frequency 230 V / 1 / 50 Hz 230 V / 1 / 50 Hz 230 V / 1 / 50 Hz Nominal consumption / Fuse 820 W / 16 A 1145 W / 16 A 1279 W / 16 A 790 x 440 x 1013 mm 790 x 440 x 1013 mm 790 x 440 x 1013 mm 68 kg 73 kg 75 kg 969 m³/h 1332 m³/h 1635 m³/h 31,9 dB (A) 31,9 dB (A) 34,8 dB (A) with earthing contact / 5 m with earthing contact / 5 m with earthing contact / 5 m Protection class IP 24 IP 24 IP 24 Compressor type Reciprocating piston Reciprocating piston Reciprocating piston Hot gas Hot gas Hot gas Pressostat switch point Off 28 bar Off 28 bar Off 28 bar Pressostat switch point thermostatic expansion valve thermostatic expansion valve thermostatic expansion valve Refrigeration unit with control Item no. 00173907 00173909 00173908 Refrigeration unit with remote control 7,5 m - Item no. 00199567 00199568 00199569 Refrigeration unit with remote control 15 m - Item no. 00199587 00199588 00199589 Refrigeration unit with bus operation - Item no. 00173387 00173388 00173389 Coldroom temperature adjustment range Ambient temperature permissible Size Control Dimensions (H x W x D) Weight Min. exhaust air volume [m3/h] at ambient temperature 32 °C and heat increase of 5 K Sound pressure level¹) Connection / length of power cable Defrosting 1) Level of sound pressure measurements taken at a distance of 10 m during ambient temperature 25°C. Depending on local conditions and installation, values can be reached above the levels given. General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 20 GB Right reserved to make technical changes! GB Designation FS 2000 FS 2500 FS 3000 -5°C to -25°C -5°C to -25°C -5°C to -25°C +1°C to +43°C +1°C to +43°C +1°C to +43°C 2 2 2 Cooling capacity (DIN EN 14511) 1990 W 2490 W 3020 W Refrigerant R404A R404A R404A Refrigerant amount 1500 g 1800 g 1800 g electronic electronic electronic Voltage / Phases / Frequency 400 V / 3 / 50 Hz 400 V / 3 / 50 Hz 400 V / 3 / 50 Hz Nominal consumption / Fuse 1660 W / 16 A 2043 W / 16 A 2496 W / 16 A 996 x 640 x 1239 mm 996 x 640 x 1239 mm 996 x 640 x 1239 mm 105 kg 109 kg 111 kg Min. exhaust air volume [m3/h] at ambient temperature 32 °C and heat increase of 5 K 1937 m³/h 2119 m³/h 3209 m³/h Sound pressure level¹) 35,8 dB (A) 37,8 dB (A) 37,5 dB (A) Connection / length of power cable CEE / 0,7 m CEE / 0,7 m CEE / 0,7 m Protection class IP 24 IP 24 IP 24 Compressor type Scroll Scroll Scroll Hot gas Hot gas Hot gas Pressostat switch point Off 28 bar Off 28 bar Off 28 bar Pressostat switch point thermostatic expansion valve thermostatic expansion valve thermostatic expansion valve Refrigeration unit with control Item no. 00173910 00173911 00173912 Refrigeration unit with remote control 7,5 m - Item no. 00199570 00199571 00199572 Refrigeration unit with remote control 15 m - Item no. 00199580 00199591 00199582 Refrigeration unit with bus operation - Item no. 00173390 00173391 00173392 Coldroom temperature adjustment range Ambient temperature permissible Size Control Dimensions (H x W x D) Weight Defrosting General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 21 GB Right reserved to make technical changes! GB 4. Capacity EVO-COOL® refrigeration units EVO-COOL® CS 900 EVO-COOL® CS 500 1800 1300 Tu = 25°C Tu = 32°C Tu = 43°C 1100 Tu = 25°C Tu = 32°C Tu = 43°C 1600 Cooling capacity [W] Cooling capacity [W] 1400 900 700 500 1200 1000 800 300 600 400 100 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 -5 25 -3 -1 1 3 5 Coldroom temperature [°C] 9 11 13 15 17 19 21 23 25 15 17 19 21 23 25 15 17 19 21 23 25 Coldroom temperature [°C] EVO-COOL® CS 1300 EVO-COOL® CS 1500 2600 2400 Tu = 25°C Tu = 32°C Tu = 43°C 2200 2000 Tu = 25°C Tu = 43°C Tu = 32°C 2400 2200 Cooling capacity [W] 1800 Cooling capacity [W] 7 1600 1400 1200 1000 2000 1800 1600 1400 1200 800 1000 600 800 400 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 -5 25 -3 -1 1 3 5 7 9 11 13 Coldroom temperature [°C] Coldroom temperature [°C] EVO-COOL® CS 2000 EVO-COOL® CS 2500 5000 3200 Tu = 25°C 3000 Tu =25°C Tu = 32°C Tu = 32°C 4500 Tu = 43°C Tu = 43°C 2800 4000 Cooling capacity [W] Cooling capacity [W] 2600 2400 2200 2000 3500 3000 2500 1800 2000 1600 1500 1400 1000 1200 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25 Coldroom temperature [°C] -5 -3 -1 1 3 5 7 9 11 13 Coldroom temperature [°C] EVO-COOL® CS 3000 5500 Tu = 25°C Tu = 32°C Tu = 43°C 5000 Cooling capacity [W] 4500 4000 3500 3000 2500 2000 1500 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25 Coldroom temperature [°C] General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 22 GB Right reserved to make technical changes! GB 5. Capacity EVO-COOL® deep-freeze units EVO-COOL® FS 900 EVO-COOL® FS 1200 2000 1800 Tu = 25°C Tu = 32°C Tu = 43°C 1600 1600 Cooling capacity [W] 1400 Cooling capacity [W] Tu = 25°C Tu = 32°C Tu = 43°C 1800 1200 1000 800 1400 1200 1000 600 800 400 600 200 -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 400 -5 -25 -24 -23 -22 -21 -20 -19 -18 Coldroom temperature [°C] -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -12 -11 -10 -9 -8 -7 -6 -5 -12 -11 -10 -9 -8 -7 -6 -5 Coldroom temperature [°C] EVO-COOL® FS 2000 EVO-COOL® FS 1400 3000 2400 Tu = 25°C Tu = 32°C Tu = 43°C 2200 Tu = 25°C Tu = 32°C Tu = 43°C 2800 2600 Cooling capacity [W] 2000 Cooling capacity [W] -17 1800 1600 1400 1200 2400 2200 2000 1800 1600 1000 1400 800 1200 1000 600 -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -25 -5 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 Coldroom temperature [°C] Coldroom temperature [°C] EVO-COOL® FS 3000 EVO-COOL® FS 2500 4000 5000 Tu = 25°C Tu = 32°C Tu = 43°C 3500 Tu = 25°C Tu = 32°C Tu = 43°C 4500 4000 Cooling capacity [W] Cooling capacity [W] 3000 2500 3500 3000 2000 2500 1500 2000 1500 1000 -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 Coldroom temperature [°C] -12 -11 -10 -9 -8 -7 -6 -5 -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 Coldroom temperature [°C] General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 23 GB Right reserved to make technical changes! GB 6. Dimensions installation size 1 CS 500, CS 900, CS 1300, CS 1500, FS 900, FS 1200, FS 1400 Evaporator height (mm) CS 500 CS 900 CS 1300 CS 1500 FS 900 FS 1200 FS 1400 353 353 453 503 353 453 503 1013 386 10 587 790 353 / 453 / 503 113 251 350 / 250 / 200 377 754 407 400 343 29 440 29 337 341 General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 24 GB Right reserved to make technical changes! GB 7. Dimensions installation size 2 CS 2000, CS 2500, CS 3000, FS 2000, FS 2500, FS 3000 Evaporator height (mm) CS 2000 CS 2500 CS 3000 FS 2000 FS 2500 FS 3000 503 553 553 503 553 553 1239 320 418 390 / 340 757 10 996 503 / 553 134 501 944 580 573 479 47 640 47 460 538 General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 25 GB Right reserved to make technical changes! GB 8. Tendering text EVO-COOL® refrigeration units Item Number Description No. Unit Price Total Price Refrigeration units EVO-COOL® CS Compact, plug-in refrigeration unit for coldroom temperatures from -5°C bis +20°C Surfaces STA= Viessmann Standard white powder coating, galvanized steel coating with antimicrobial Viessmann SmartProtec® powder coating (similar to RAL 9016). EST= Austenitic stainless steel (1.4301) - Special design polished or brushed - on request Scope of delivery and delivery state: Stable housing for attaching to a coldroom element or a wall with a thickness from 60 to 150 mm. Axial fans with grid, Defroster drain tubing with electrical heating unit, Defrost water evaporation plate with safety run-off, Electronic temperature control, Hot gas defrost, Condenser with variable speed fan and a microchannel heat exchanger. Control with text display, self diagnosis, remote maintenance, Bus operation, USB data transfer and internet connectivity. Potential-free alarm, audible alarm when faults, with fault memory, Connection for door contact switch, Cable with earthing contact plug or CEE socket. Optional: Data logger, Filter fabric, Winter regulation, Sound-insulated housing design. Complete refrigeration equipment consisting of: Hermetically sealed condenser with winding protection switch and unloaded start, Thermostatic expansion valve, Collector dryer, Pressure safety monitor, timed defrost by hot gas with safety temperature monitor or air defrosting at coldroom temperature higher than +5 ° C (adjustable), Pump-out function (activated), 5 m cable with earthing contact (CS 0500, 0900; 1300, 1500, 2000), 700 mm cable with CEE socket (CS 2500, 3000), Refrigerant R 134a. Cooling capacity at coldroom temperature +5°C and temperature ambient +32°C: ________________________ Watt Cooling temperature range: -5°C to +20°C Admissible ambient temperature: +1°C to +43°C Power supply: AC 230 Volt ~, 50 Hz bei CS 500, 900, 1300, 1500, 2000 AC 400 Volt 3N~, 50 Hz bei CS 2500, 3000 Power consumption Cooling: ________________________ Watt Defrosting: ________________________ Watt Current consumption Cooling: ______________________ Ampere Defrosting: ______________________ Ampere Dimensions (height x width x depth) 790 x 440 x 1013 mm at CS 0500, 0900, 1300, 1500 996 x 640 x 1239 mm at CS 2000, 2500, 3000 Weight: ________________________ kg General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 26 GB Right reserved to make technical changes! GB 9. Tendering text EVO-COOL® deep-freezing units Item Number Description No. Unit Price Total Price Deep-freezing units EVO-COOL® FS Compact, plug-in refrigeration unit for coldroom temperatures from -5°C bis -25°C Surfaces STA= Viessmann Standard white powder coating, galvanized steel coating with antimicrobial Viessmann SmartProtec® powder coating (similar to RAL 9016). EST= Austenitic stainless steel (1.4301) - Special design polished or brushed - on request Scope of delivery and delivery state: Stable housing for attaching to a coldroom element or a wall with a thickness from 60 to 150 mm. Axial fans with grid, Defroster drain tubing with electrical heating unit, Defrost water evaporation plate with safety run-off, Electronic temperature control, Hot gas defrost, Condenser with variable speed fan and a microchannel heat exchanger. Control with text display, self diagnosis, remote maintenance, Bus operation, USB data transfer and internet connectivity, With scroll compressors with direction relays. Potential-free alarm, audible alarm when faults, with fault memory, Connection for door contact switch, Cable with earthing contact plug or CEE socket. Optional: Data logger, Filter fabric, Winter regulation, Sound-insulated housing design, Sound-insulated design scroll compressor (only by FS 2000, 2500, 3000). Complete refrigeration equipment consisting of: Hermetically sealed condenser with winding protection switch and unloaded start, Thermostatic expansion valve, Collector dryer, Pressure safety monitor, timed defrost by hot gas with safety temperature monitor or air defrosting at coldroom temperature higher than +5 ° C (adjustable), Pump-out function (activated), 5 m cable with earthing contact (FS 0900, 1200; 1400), 700 mm cable with CEE socket (FS 2000, 2500, 3000), Refrigerant R404A. Cooling capacity at coldroom temperature -18°C and temperature ambient +32°C: ________________________ Watt Cooling temperature range: -5°C to -25°C Admissible ambient temperature: +1°C to +43°C Power supply: AC 230 Volt ~, 50 Hz bei FS 0900, 1200,1400 AC 400 Volt 3N~, 50 Hz bei FS 2000, 2500, 3000 Power consumption Cooling: ________________________ Watt Defrosting: ________________________ Watt Current consumption Cooling: ______________________ Ampere Defrosting: ______________________ Ampere Dimensions (height x width x depth) 790 x 440 x 1013 mm at FS 0900, 1200, 1400 996 x 640 x 1239 mm at FS 2000, 2500, 3000 Weight: ________________________ kg General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 27 GB Right reserved to make technical changes! GB General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 28 GB Right reserved to make technical changes! GB General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 29 GB Right reserved to make technical changes! GB Viessmann Kühlsysteme GmbH Schleizer Straße 100 D-95030 Hof/Saale Germany Phone +49 (0) 9281/814-0 Fax +49 (0) 9281/814-269 kuehlsysteme@viessmann.de www.viessmann.de/kuehlsysteme Your responsible refrigeration service: General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement. Page 30 GB Right reserved to make technical changes!